DX - Quick Start Guide Configuration
(Three-Phase Input)
QUICKSTART DX, Revision 002
Typical Configuration:
Analog Constant Pressure Setup
Setup Constant Pressure |
Yes (Enter) No (Home) |
- On start, use the arrows to toggle to “RUN CONSTANT PRESSURE WIZARD?” - Press ENTER key to proceed.
- "SPEED REFERENCE" - Select how speed reference is controlled between Start/Stop, 4-20mA, and 0-10 VDC using arrows to toggle. Press ENTER to proceed.
- “4-20mA psi RANGE" - Set the psi range of the 4-20mA sensor. Default is 150 psi. Press ENTER to proceed.
- “psi SETPOINT” - Determines the pressure you want to maintain. The factory default is 50 psi. Use the arrow keys to change if desired. Press ENTER to proceed.
-
"SUBMERSIBLE PUMP” - This parameter sets the ramp profile for a submersible pump. “Yes” - ramps to 30 HZ in the first second to prevent excessive wear on the thrust bearing. "No" - The frequency will increase in a linear fashion from zero to max frequency. Use the arrow keys to toggle between the two settings.
Press ENTER to proceed. - "DISABLE MANUAL MODE" - The "Yes" value allows you to disable the MANUAL button run mode. "No" allows you to run the VFD manually on/off max frequency.
- "OVERCURRENT LIMIT" - Setting for motor overload protection (service factor amp rating for the motor) using the arrows to toggle. Press ENTER to proceed.
- Press the RUN/AUTO button to start the pump.
- Motor rotation must be verified upon completion of setup.
- If the VFD is not going to sleep, first check for leaks. If no leaks are present, increase the “Shutoff Frequency” under “Constant Pressure Parameters.”
- Set pressure tank psi to 70% of VFD psi Setpoint.
- Any of these settings can be modified if needed after the initial setup completes. For a full listing of available parameters, please refer to the product manual.