QUICKSTART 3LH, Revision 002
Typical Configuration:
Analog Constant Pressure Setup
Setup
Constant Pressure
|
Yes (Enter)
No (Home)
|
-
On start, use the arrows to toggle to “RUN CONSTANT PRESSURE WIZARD?” - Press ENTER key to proceed.
-
"SPEED REFERENCE" - Select how speed reference is controlled between Start/Stop, 4-20mA, and 0-10 VDC using arrows to toggle. Press ENTER to proceed.
-
“4-20mA psi RANGE" - Set the psi range of the 4-20mA sensor. Default is 150 psi. Press ENTER to proceed.
-
“psi SETPOINT” - Determines the pressure you want to maintain. The factory default is 50 psi. Use the arrow keys to change if desired. Press ENTER to proceed.
-
"SUBMERSIBLE PUMP” - This parameter sets the ramp profile for a submersible pump. “Yes” - ramps to 30 HZ in the first second to prevent excessive wear on the thrust bearing. "No" - The frequency will increase in a linear fashion from zero to max frequency. Use the arrow keys to toggle between the two settings.
Press ENTER to proceed.
-
"DISABLE MANUAL MODE" - The "Yes" value allows you to disable the MANUAL button run mode. "No" allows you to run the VFD manually on/off max frequency.
-
"OVERCURRENT LIMIT" - Setting for motor overload protection (service factor amp rating for the motor) using the arrows to toggle. Press ENTER to proceed.
-
Press the RUN/AUTO button to start the pump.
Additional Notes:
-
Motor rotation must be verified upon completion of setup.
-
If the VFD is not going to sleep, first check for leaks. If no leaks are present, increase
the “Shutoff Frequency” under “Constant Pressure Parameters.”
-
Set pressure tank psi to 70% of VFD psi Setpoint.
-
Any of these settings can be modified if needed after the initial setup completes. For a full listing of available parameters, please refer to the product manual.